|
The control of gases to a process chamber seems like a
straight forward task to accomplish. However, the problems
encountered can have serious results. Improper flow control can
cause rejected product, longer than expected processing time, or
even catastrophic system failure due to improper system pressure
or leaks. In general, mass flow control problems can be separated
into three types, (1) Intrinsic to the flow control device, (2)
Systematic problems, and (3) Environmental effects.
Environmental effects are the easiest to identify and correct.
Examples of environmental effects are changing thermal
environment, vibration, exposure to high levels of RF
Interference, etc. The identification and removal of such
existing conditions will make it easier to identify and correct
problems in the other two categories.
Systematic problems are the hardest problems to separate from
others. Often they do not exist except under certain process
conditions. Systematic problems are often mistaken for problems
intrinsic to the flow controller. Some common systematic problems
are changing or unstable system pressures, changing process gas
temperatures, valve sequencing and timing, system pumping speed,
process gas quality, etc. All of these factors have an effect on
the gas delivery devices. Understanding the effects can allow the
process engineer to eliminate or compensate for those that have
detrimental effects on gas delivery.
The flow controllers available from all manufacturers share
some critical intrinsic characteristics and therefore problems.
These are due in large part to the sensing technique and bypass
arrangement used to allow different flow rates of instruments to
be produced. The most significant intrinsic performance problem
areas:
- Linearity and performance problems associated with Gas
Correction Factors used in calibration for gases other
than the calibration gas.
- Zero drift
- Free convection in the sensor (thermal siphoning)
- Controller oscillation
- Seal degradation and leaks
- Overshoot
Other problems reported with repeatability or linearity are
usually manifestations of one or more of the problems specified
above.
With the understanding that gas delivery problems come from
several areas, the approach to their solutions must encompass the
areas identified and be rigorous in nature. In the pages that
follow, a logical approach to identifying and solving many common
mass flow control problems is presented. Following this approach
will at least ensure the process engineer that he has looked
beyond the flow control device to address the desired gas
delivery.
Avoiding Problems
As with most problems, those occurring in flow control can be
diminished greatly through understanding the operation of the
device. This will allow the process engineer to adjust for the
limitations of the flow controller and the manufacturer to
understand the most critical functions required of the device.
Sensor Operation: Set Point Repeatability -
Accuracy - Zero Drift
These performance functions are lumped together because they
are interrelated in the flow controller design. A brief and
generalized explanation of the operation of the thermal mass flow
sensor element will aid in illustrating the relationships and
inherent shortcomings of the devices.
Theory of Operation - Sensor
Two physical components make up the sensing element of a flow
controller, (1) a thin-walled small diameter stainless steel tube
with multiple high temperature coefficient windings applied to
the external diameter, and (2) a secondary flow channel or bypass
through which the bulk of the gas flows. Since the inlet and
outlet of both components are coincident the pressure drop across
each is equivalent. In theory, flow split ratio remains constant
through the entire flow range of the instrument. The total flow
through the instrument is inferred by measuring the flow through
the sensor tube and then adding the amount (determined by the
ratio) flowing through the bypass. The amount of gas flowing
through the tube is measured by excitation of the sensor tube
windings with electrical current and noting voltage differences
that occur as flow is varied. These voltage differences are then
referenced to the aero-flow voltage difference (if any) and used
as a direct indication of flow. Since a gas property dependent
upon mass rate of flow is inferred (heat capacity) this voltage
output is proportional to mass flow of the gas.
Inherent Limitations
Because the flow sensing technique is thermal in nature, all
heat transfer modes affect the flow indication. The heat transfer
modes that exist in the sensor are:
- Free convection, both to the sensor environment and to
the process gas at zero flow
- Conduction along the tube, and to insulating media
- Radiation heat transfer
Changes in any of the above quantities can have an effect on
the performance of the MFC. The largest detrimental effect is
from a change in free convection to or from the environment. This
can be caused in several ways, one of which is an internal (to
the MFC sensor cover) change in temperature or temperature
gradient caused by the heating of the valve or an electrical
component. This temperature change can cause the natural zero to
shift resulting in corresponding shift in calibration.
Another limitation of this sensing technique, inherent in flow
controller design is aging of the sensor. Fine resistance wire is
wound on the tube in a specific pattern and with a specific
tension. Through expansion and contraction caused by heating and
cooling of the sensor tube and wire elements these patterns and
tensions change. These changes can cause a zero drift or even a
change in sensitivity of the sensor, due to the change in heat
transfer quantities from the moving or sifting of the heating
element/temperature sensing wire.
Free convection to the process gas at zero flow (thermal
siphoning) has been recognized recently as a significant problem.
This problem is reported virtually exclusively in flow
controllers that are mounted vertically in a system. A zero shift
is observed due to heated gas rising in the sensor tube and
cooling upon exit. This sets up a real flow through the sensor
and the bypass and is not an indication that the natural zero has
changed. The danger here is that if this non-natural zero output
is adjusted, a calibration error will result.
Minimizing Inherent Problems
Both the manufacturers and users of mass flow controllers must
recognize the factors that minimize sensor drift as stated above.
Most major MFC manufacturers have now realized the value of
extended or accelerated burn- in of their sensor prior to
assembly into the controller. Some manufacturers are burning-in
sensors for as long as two weeks prior to assembly. Many
manufacturers have introduced circuity features such as
temperature compensation and auto-zero circuits that attenuate or
mask internal thermal effects. These work well for the most part
with one outstanding limitation: auto-zero circuits will create a
calibration error in virtually all cases when used to zero the
drift associated with thermal siphoning.
MFC users can enhance the performance of the flow controller
by doing several things. First, always allow a flow controller to
warm-up thoroughly. Second, where possible do not adjust the
natural zero of the flow controller but instead record it and
adjust as necessary in external control electronics. Last, if
space allows, do not mount the flow controller in a vertical
position. If this practice is avoided, thermal siphoning should
not be a problem. If vertical mounting is unavoidable, do not
adjust the no-flow, zero, output.
Environmental and Systematic Effects
Several environmental and systematic conditions will have an
effect on the performance of the sensing element. Many of these
conditions can be eliminated through system design and others
reduced to the point where they are manageable.
Again, because the sensing technique is thermal, the operation
of the MFC is influenced by changing temperatures of its
environment. If the temperature in which the MFC operates changes
significantly, the zero output of the device may seem to track
these changes. This will result in calibration shifts and may
show up as a repeatability problem.
Because of the construction of the sensor element (fine wires
wrapped around a capillary tube), it acts as a very effective
antenna. When exposed to high levels of Radio Frequency
Radiation, the output of the sensor can be effected. The sensor
has an inherently low raw signal to noise ratio, so when this
interference is received it is amplified along with the flow
signal. This can create a control band around the desired set
point that is not as precise as desired and can create controller
oscillation that renders the device useless.
Valve sequencing can cause many of the systematic problems
encountered with flow control. A common scenario is as follows:
during a manufacturing process, a pneumatic on/off valve external
to the MFC is closed while a non-zero set point is applied to the
MFC. The MFC internal control valve will open to its maximum in
an effort to maintain the desired flow through the MFC. The
system is then pumped-out until a specified vacuum is reached and
the process is then restarted by opening the pneumatic on/off
valve. Extreme overshoot with possible oscillation and long
settling times can result. This is due to the change in system
pressure and gas composition within the flow controller itself.
Further, with the set point left on , the control valve will
respond by driving full open, creating more internal heat. All
these factors work to change the thermal equilibrium and
therefore change the natural zero of the MFC. As the process is
restarted, the thermal equilibrium of the sensor is upset once
again and the oscillation and overshoot mentioned above may
occur.
Another effect that has been erroneously discounted is
changing process gas (supply gas) temperature. These effects are
seen more on a day-to-day rather than a run-to-run basis and are
often mistaken for long-term drift of the MFC. To understand the
mechanism that accounts for this calibration change, we must
remember that the sensor element is actually two components, the
sensor tube and the MFC bypass. The ratio of the flow passing
through this combination is dependent upon their hydraulic
diameters providing that the Reynolds Numbers in each are
compatible and maintain a consistent ratio. The Reynolds
Number is a function of velocity, diameter (or hydraulic
diameter), density, and kinematic viscosity. Density is extremely
temperature dependent for most gases used. This means that if the
density of the gas passing through the tube varies
disproportionately to the density of gas passing through the
bypass, the bypass ratio and therefore the calibration will
change. This will happen if the supply gas temperature changes.
With up to 10 degree swings in temperature, the bulk average
temperature of the gas passing through the sensor tube remains
constant (the capillary tube is a very efficient heat exchanger),
but the gas passing through the bypass retains the variation in
temperature and thus density, creating the density change that
effects the bypass ratio and therefore calibration.
Process gas composition and quality, especially the presence
of moisture, has an effect on both calibration and performance of
an MFC. With varying compositions, the heat capacity of the gas
changes and the calibration will be effected. Moisture can have
the same effect, or worse, it can cause acids such as HCl to form
in the flow controller. These acids can degrade seals and create
leaks or have a more insidious effect of combining with other
compounds to form clogs inside the sensor tube or bypass. This
can cause very large changes in the MFC calibration (sensitivity)
or the MFC performance (speed of response).
Eliminating Environmental and Systematic
Effects
Keeping the MFCs in an environment maintained at a relatively
constant operating temperature and one that acts as a shield
against RF Interference is the first and easiest step to take
toward ensuring proper and consistent flow controller operation.
Further, properly grounding the cable shield and isolating the
electrical common from RF interference will achieve notable
results.
Sequencing valves to keep the flow controller exposed to the
process gas at relatively constant pressure will help eliminate
zero-shifts , overshoot and oscillation.
Conditioning of the process gas will greatly enhance the
performance of the gas delivery system. Gas purity should be
monitored, with filters and dryers installed to eliminate
moisture and other unwanted trace elements. Also, heat exchangers
in the supply line used to control the temperature of the supply
gas to within reasonable limits of +/-2 degrees will improve
day-to-day repeatability of the gas delivery system.
MFC Operation: Valve-Oscillation-Inadequate
Flow-Speed
A thermal mass flow controller is a complete closed-loop
feedback (or feed-forward) system. This is a very complex system
dependent upon the operation of discreet components with varying
performance characteristics and time constants. Signal
amplifiers, linearizers, PID circuits, valve drive circuits, and
constant current generators are among the components found in
these small packages. Though the manufacturers specify large
operating ranges of temperature, pressure (and differential
pressure), gases, and flow rates, they do not guarantee that all
performance specifications are valid under all conditions.
Because of the dependence of operating specifications on
operating conditions, users should communicate as much
information as possible about the actual operating conditions of
the MFC to the manufacturers. If this is done, optimum
performance can be tuned around these conditions. The use of
generic flow controllers will not assure optimum performance. (A
generic mass flow controller is one that is provided by the
supplier with a nitrogen calibration, or another non- actual
system gas, and no operating pressures, temperatures, or
orientation specified.)
Intrinsic, Systematic, and Environmental
Problems
The performance of the MFC, as a system, makes it impossible
to decouple the three types of problem causing effects.
Fortunately most are easily understood and corrected.
The mass flow controller valve is, in general, made up of (1)
a motive force (electromagnetic, thermal, piezo- electric,
motor-driven, etc.), (2) a resistive force (spring, diaphragm,
etc.), and (3) a variable flow restriction (orifice-poppet,
orifice-ball, etc.). The motive force is activated by the control
circuitry to act against the resistive force to vary the flow
restriction. Virtually all of the pressure drop across the flow
controller takes place across the control valve.
Proper performance of the valve is determined by all of these
components being sized properly for the intended actual gas used,
range and differential pressure of the system. Problems can occur
in several ways. First, the valve restriction or orifice must be
sized correctly. An orifice that will pass 100 sccm of Nitrogen
when fully opened at 30 PSID may not pass 100 sccm of Nitrogen at
5 PSID. Further, this orifice may not pass 100 sccm of WF6 at
either condition. This is because the orifice is too restrictive
for the heavier gas. Oscillation can also occur if the resistive
force or valve spring is too heavy or too light for the
application. A spring with an appropriate spring rate for
nitrogen may work fine if used for BCl3 or Argon but can cause
oscillation in Hydrogen or Helium.
The differential pressure across the flow controller can be
created by elevated upstream pressure or by the creation of a
vacuum downstream. This can have a substantial effect upon system
performance. As discussed, the exposure of the sensor to vacuum
can have performance effects. Further, system time constants such
as sensor speed of response change radically under these
conditions. The PID control circuitry may not have the margin to
provide optimum response under both conditions and possibly must
be tuned to the correct application or oscillation or long
settling times may result.
Avoiding the Problems
The above problems can virtually all be eliminated by
characterizing the gas delivery operating conditions and
communicating them to the manufacturer or service facility when
ordering a flow controller or having one serviced. Further,
never apply a generic flow controller to a critical requirement;
always have it re-tuned and properly labeled for the specific
application.
Minimizing the changes seen by the flow controller will also
help eliminate systematic problems. Keeping the controller
pressurized with the process gas can eliminate oscillation and
over-the-hill conditions that can occur.
Other Applications Problems
Long Cable Lengths
Because many flow controllers do not draw the same current
from the positive and negative supply voltages, current is
present on the reference common. For short (low resistance) cable
lengths this is not a problem. In applications with longer cable
lengths having significant wire resistances, the effect may be
that the displayed output signal and the set point signal will
not match.
Gas Correction Factor
Due to internal geometries and operating regimes (temperature,
Reynolds Number, etc.) gas correction factors vary from MFC
manufacturer to manufacturer. Further, the accuracy of some gas
correction factors is no better than +/-10% and is flow
dependent. The derivation of gas correction factors is the
subject of another complete paper but, the recommendation is to
use the manufacturer specified factor and take steps to ensure
absolute repeatability, not accuracy.
Summary
The performance of thermal mass flow controllers is affected
by many factors. These have been divided into intrinsic,
systematic, and environmental effects. The best way to ensure the
performance of the gas delivery system is to minimize the causes
for error. The major actions that can be taken to eliminate flow
control problems are listed below.
- Choose MFCs from manufacturers that burn-in the sensors
prior to assembly.
- Always allow MFCs to warm-up completely under approximate
operating conditions before recording the natural zero or
flow values.
- Where possible, do not adjust MFC calibration pots
in-situ; rather record output changes and compensate
externally, by changing the set point to the MFC.
- Where possible, prevent thermal siphoning by not mounting
the MFC in a vertical position. When vertical mounting is
unavoidable, do not activate an auto zero circuit or
manually adjust flow controller zero output in-situ.
- Keep flow controllers in a thermally stable or controlled
environment.
- Properly shield flow controllers and cabling from RF
interference, and isolate circuit common from case
ground.
- Sequence shut-off valves to maintain a stable pressure
condition and gas composition if possible in the flow
controller.
- Supply clean, pure, and dry process gas to the flow
controller.
- Control the temperature of the process gas to the flow
controller from run-to-run and day-to-day.
- For all critical applications, use an MFC calibrated and
tuned for the actual gas and range to be used; do not use
a generic MFC.
- Do not expose MFCs to sudden pressure surges or leave
them with no process gas pressure with a non-zero
set-point commanded.
- Avoid long cable lengths with flow controllers drawing
power unevenly from the power supply rails.
- When a gas correction factor is necessary, always use the
test gas and CF value specified by the flow controller
manufacturer.
- Always communicate as close to the actual operating
conditions as possible to the MFC manufacturer or service
facility when ordering an MFC or having an MFC serviced.
Most flow controller problems can be eliminated or diminished
significantly through understanding the effects on these
complicated devices. Communication of the most critical process
parameters to the vendor is the best way to ensure that the flow
controller will perform as required. As always, with any
equipment you operate, read the operating manuals before using
the equipment!
|