|
The specification on mass flow controller valve closure references the amount of gas that will leak
past the control valve when a zero flow set point is given and a specified pressure differential applied across
the device. In this case the gas does not leak out of the flow device but past the valve and into the downstream
flow path. This is not usually a problem with elastomer seal devices since the amount of leakage is essentially zero,
but with metal seals positive shutoff is not possible because the sealing surfaces are metal-to-metal with a limited
amount of closure force available. The manufacturers specify an accepted leak through rate, usually in percent of
full scale or in mv output (50 mv equals 1% full scale on a 5 volt full scale output device).
Since this is actually the measurement of a gas leak through an orifice (the gap in the valve seat) it is also very
dependent on the density of the gas used for the test.
While most manufacturers of metal seal controllers use 1% of full scale as their specification
(largely because some of the larger gas panel suppliers have adopted this as their specification) there are some
that are unable to meet this specification and in some cases the specification for leakage is not referenced
directly at all in their performance data, possibly because it is much higher than their competitors. In these
cases the issue is indirectly addressed by a statement in the performance spec that the device should not be used
as a positive shutoff.
It is usually possible to achieve much better results than the published specification with a new device
(depending on the gas density) since the sealing surfaces are new and unblemished by use. As the valve is
subjected to the forces and wear of many closures there is inevitable wear on the surfaces that can cause
deterioration in the effective closure and a gradual increase in the leakage rate over time. When such a
device is returned for service it is possible that, although the closure has degraded appreciably, it will
still meet the specification but will not be as good as it was when new. Unless there is some reason to
believe that the valve closure required is better than the specification the device is not adjusted as long
as it meets the published value.
Since the valve leakage spec is referenced as a percent of full scale the leak rate will be proportional
to the full scale flow of the device, which means that the valve leakage on a 100 sccm device could be 10
times that of a 10 sccm device and still meet factory specs. A test based solely on a specific rate of rise
in downstream pressure over time will selectively fail the higher flow device since it is looking for a specific
flow rate as opposed to a flow rate at a certain percent of full scale. If your process is setup to pass/fail on
valve closure tests results that are much lower than the factory spec or run higher differential pressures expect
higher failure rates (even on new devices) and repair costs to replace valve components on older devices with some
run time on them.
If you have been using elastomer type devices and are switching to metal seal devices it would be wise to
modify your testing procedures for valve closure and install positive shutoff valves up and downstream of your
flow devices.
In summary metal seal flow controllers are not positive shutoff devices and are not claimed to be. There
are factory specifications for the accepted leak rate that are considered acceptable although not always
experienced, especially on new devices. Lack of knowledge about valve leakage issues and what your process
requires can cause undue incoming test failures and repair costs.
Call us at 1-800-632-4357 to discuss these or any other flow control issues that you may have.
|